Aerial Insulated Cable 10kv
1.Standars
The Aerial Insulated Cable meets the China’sstandard of GB/T14049-2008
International standard also can besatisfied because we are manufactures.
And customer special request can be fulfilledtoo.
2.Applications
a.Copper Conductor or Aluminum Conductorwith XLPE or HDPE insulation Aerial Cable is suiltable for aerial power lines with A.C. rated voltage U/Um upto 10/12kv and 35/42kv
b.The soft copper conductor cable is usedas lead of transformer.A certain distance should be kept between cable andtrees during installation. Frequently touching between cables and trees isallowed during operation.
c.Only short time touching Allowed duringoperation for light duty type JKLY/Q,JKLGY/Q, JKLYJ/Q,JKLGJ/Q.
4.Specification
Type | No. of Cores | Rated Voltage | |
10 kv | 35 kv | ||
Nominal Cross-section Area mm² | |||
JKLYJ JKTRYJ JKLGYJ | 1,3 | 35~300 | 50~300 |
JKTRY | 1 | 35~300 | |
JKLY JKLGY | |||
JKLY/Q,JKLGY/Q | |||
JKLYJ/Q,JKLGJ/Q | 1 | 10~300 |
5.Using Properties
a.Rated Volatge:10kv
b.Cable installation temperature not lessthan -20°C
c.Max. temperature of cable at shortcircuit(The max. duration does not exceed 5 minutes)
For XLPE insulation is 250°C.
For HDPE insulation is 150 °C.
d.The Max. bending radius of cable shallnot be less than 20(D+d)mm(D and d represent the nominal overall diameter ofcable and diameter of conductor )
Technical Specification
JKLYJ 10KV | ||||||
Cross-section Area | Thickness of Insulation | Approx. Overall Dia. | Max. Resistance of Conductor at 20 °C | Min. Breaking Load of conductor | Approx. Weight of Cable | |
mm² | mm | mm | Ω/km | N | kg/km | |
35 | 3.4 | 14.8 | 0.868 | 5177 | 300.8 | |
50 | 3.4 | 16.1 | 0.641 | 7011 | 359.8 | |
70 | 3.4 | 17.8 | 0.443 | 10354 | 441.0 | |
95 | 3.4 | 19.6 | 0.320 | 13727 | 548.0 | |
120 | 3.4 | 21.0 | 0.253 | 17339 | 643.0 | |
150 | 3.4 | 22.6 | 0.206 | 21033 | 753.6 | |
185 | 3.4 | 24.2 | 0.164 | 26732 | 877.3 | |
240 | 3.4 | 26.4 | 0.125 | 34679 | 1061.3 | |
300 | 3.4 | 28.6 | 0.100 | 43349 | 1263.7 |
Cross-section Drawing
Aerial Insulated Cable 10kv